The 280C M-Bus Concentrator is an automatic data collection device designed for M-Bus meters such as 280T BTU meter, 280W water meter and STE-xx electric meter. The concentrator and the M-Bus meter communicate by the industry standard M-Bus interface.
(1) 280C-0: This is a transparent M-Bus concentrator. It provides M-Bus power to M-Bus meters, and passes the M-Bus protocol to upper layer device. Sometimes it is called M-Bus convertor.
The interface to the upper layer device could be M-Bus (280C-0-0) or RS232 (280C-0-1).
(1) 280C-1: This is an intelligent M-Bus concentrator with large storage for scheduled meter reading. It provides M-Bus power to M-Bus meters, automatically reads data from those M-Bus meters, stores those data, and transmits those data to upper layer upon request.
The interface to the upper layer device could be M-Bus (280C-1-0) or RS232 (280C-1-1).
(1) 280C-2:This is a transparent M-Bus to BACnet converter. It provides M-Bus interface on one side, and BACnet on the other side.
Each concentrator is able to support up to 300 M-Bus meters. It can be cascaded to form a hierarchical topology, where a large number of meters can be networked. The figure below illustrates a simple hierarchical system. The concentrator on the top is 280C-0-1, which connects to a computer on one side, and connects to several 280C-0-0 type sub layer concentrators.
The topology of using BACnet Concentrator (280C-2) is illustrated on the second figure below.
Hierarchical topology of an AMR system using M-bus concentrator.
Hierarchical topology of an AMR system using M-bus concentrator.
M-Bus Concentrator (280-0 / 280C-1)
- Transmit data upward, transfer command downward
- Large non-volatile flash memory for data storage (280C-1 only)
- Powerful communication capabilities
- Automatic meter reading (280C-1 only)
Operator only needs to set up a schedule on the time and the clients the meter value are to be taken. The concentrator collects and reports the data automatically, reliably and efficiently.
- Interface - Downward: M-bus. Default to 2400Bps. Support up to 300 devices
- Interface - Upward: For 280C-x-0 concentrator:
M-Bus, default to 2400Bps
Protocol: M-Bus
For 280C-x-1 concentrator:
RS232 (optional RS485-toRS232 adapter or USB-to-RS232 adapter), default to 2400Bps
Protocol: proprietary
-
Power:110VAC or 240VAC, 20Watts
BACnet Concentrator (280C-2)
- Transmit data upward, transfer command downward
- Support BACnet /IP. Easy to connect to the Internet
- Standard Ethernet communication
- Support BACnet AI, AO, BI, BO, PG, File and Device
- Large non-volatile flash memory for data storage
- Self-protection over power shutdown
- Interface - Downward: M-bus. Default to 2400Bps. Support up to 300 devices
- Interface - Upward: BACnet /IP. Ethernet: full duplex, 10M / 100M, self-adaption
-
Power:110VAC or 240VAC, 20Watts
|